[php snippet=1]
XCAN-AC
Generator-to-J1939
The XCAN-AC collects analog information from a generator for broadcast on the J1939 CANbus. Upon power up, the module broadcasts AC VOLTS, AMPS, FREQUENCY, PHASE ANGLE, KW, POWER FACTOR, KVA and TOTALIZING KWH. The XCAN-AC can be installed independently or with the generator display versions of the MVP SERIES, MX SERIES, C SERIES, CX SERIES or XL SERIES controllers and panels.
Jumpers provide for easy-to-configure settings. The module is water tight with water tight, plug and play connectors. LED's are provided to identify unit power and CANbus activity.
Electrical
• Operating Voltage: 6VDC to 32VDC
• Power Consumption: 100mA Nominal; 40mA Standby
• Reverse Polarity Protection: YES
• Transient Voltage Protection: YES
• Load Dump Protection: YES
Communications
• J1939 CANbus
• Optional RS485
Physical
• Enclosure: Deutsch EEC-352X4A, GORE Vented (IP67)
• Approx. Shipping Weight: 12 oz.
• Approx. Dimensions: 1.25"H x 5"W x 1.5"D.
Temperature
• Operating/Storage Range: -40°F/-40°C to 176°F/80°C
LED Indications
• Power On, CANbus Active
Configuration
• Factory Configuration
• Configurable with CI STATION
AC Specifications
Dielectric Isolation:
3000VDC 1 Minute, AC Neutral to DC Ground
4000VDC AD Neutral to Ground
AC Voltage Measure: 3-Phase, True RMA 0-600 Volts Wye or Delta Config.
AC Voltage Input Impedance: >1mOhm
Volts Ranging: 0-150V, 150-300V, 300-600V Auto Ranging
Volts Accuracy: 0.2% of Full Scale +/- 1 Count
AC Current Measure: 3-Phase, True RMS 0-5 Amps
CT Burden Resistance: 50mOhm
Current Ranging: 0-2.5A, 2.5-5.0A Auto Ranging
Current Accuracy: 1% of Full Scale +/- 1 Count
Full Scale CT Ratios: 50, 75, 100, 200, 250, 300, 400, 500, 600, 800, 1000, 1200
Frequency Measure: 0-70Hz, Aero-Cross Detection
Frequency Accuracy: 0.1Hz, +/- 1 Count
Additional Parameters Available: Power Factor, Lead/Lag, KVA, KWH